2023 Consumer Confidence Report Data
DICKEYVILLE WATERWORKS, PWS ID: 12200947
Este informe contiene información importante acerca de su agua potable. Haga que alguien lo traduzca para usted, o hable con alguien que lo entienda.
Dlaim ntawv tshaabzu nuav muaj lug tseemceeb heev nyob rua huv kws has txug cov dlej mej haus. Kuas ib tug paab txhais rua koj, los nrug ib tug kws paub lug thaam.
Water System Information
If you would like to know more about the information contained in this report, please contact Dale E Neis at (608) 568-3151.
Opportunity for input on decisions affecting your water quality
The village board of the Village of Dickeyville meets every second Wednesday in Room A of the Dickeyville Community Center, 500 East Avenue at 6 PM.
Health Information
Drinking water, including bottled water, may reasonably be expected to contain at least small amounts of some contaminants. The presence of contaminants does not necessarily indicate that water poses a health risk. More information about contaminants and potential health effects can be obtained by calling the Environmental Protection Agency's safe drinking water hotline (800-426-4791).
Some people may be more vulnerable to contaminants in drinking water than the general population. Immuno-compromised persons such as persons with cancer undergoing chemotherapy, persons who have undergone organ transplants, people with HIV/AIDS or other immune systems disorders, some elderly, and infants can be particularly at risk from infections. These people should seek advice about drinking water from their health care providers. EPA/CDC guidelines on appropriate means to lessen the risk of infection by cryptosporidium and other microbial contaminants are available from the Environmental Protection Agency's safe drinking water hotline (800-426-4791).
Source(s) of Water
Source ID
Source
Depth (in feet)
Status
1
Groundwater
870
Active
2
Groundwater
902
Active
To obtain a summary of the source water assessment please contact, Dale E Neis at (608) 568-3151.
Educational Information
The sources of drinking water, both tap water and bottled water, include rivers, lakes, streams, ponds, reservoirs, springs and wells. As water travels over the surface of the land or through the ground, it dissolves naturally occurring minerals and, in some cases, radioactive material, and can pick up substances resulting from the presence of animals or from human activity.
Contaminants that may be present in source water include:
-
Microbial contaminants, such as viruses and bacteria, which may come from sewage treatment plants, septic systems, agricultural livestock operations and wildlife.
-
Inorganic contaminants, such as salts and metals, which can be naturally- occurring or result from urban stormwater runoff, industrial or domestic wastewater discharges, oil and gas production, mining or farming.
-
Pesticides and herbicides, which may come from a variety of sources such as agriculture, urban stormwater runoff and residential uses.
-
Organic chemical contaminants, including synthetic and volatile organic chemicals, which are by-products of industrial processes and petroleum production, and can also come from gas stations, urban stormwater runoff and septic systems.
-
Radioactive contaminants, which can be naturally occurring or be the result of oil and gas production and mining activities.
In order to ensure that tap water is safe to drink, EPA prescribes regulations that limit the amount of certain contaminants in water provided by public water systems. FDA regulations establish limits for contaminants in bottled water, which shall provide the same protection for public health.
Definitions
Term
Definition
AL
Action Level: The concentration of a contaminant which, if exceeded, triggers treatment or other requirements which a water system must follow.
HA and HAL
HA: Health Advisory. An estimate of acceptable drinking water levels for a chemical substance based on health effects information. HAL: Health Advisory Level is a concentration of a contaminant which, if exceeded, poses a health risk and may require a system to post a public notice. Health Advisories are determined by US EPA.
HI
HI: Hazard Index: A Hazard Index is used to assess the potential health impacts associated with mixtures of contaminants. Hazard Index guidance for a class of contaminants or mixture of contaminants may be determined by the US EPA or Wisconsin Department of Health Services. If a Health Index is exceeded a system may be required to post a public notice.
Level 1 Assessment
A Level 1 assessment is a study of the water system to identify potential problems and determine, if possible, why total coliform bacteria have been found in our water system.
Level 2 Assessment
A Level 2 assessment is a very detailed study of the water system to identify potential problems and determine, if possible, why an E. coli MCL violation has occurred or why total coliform bacteria have been found in our water system, or both, on multiple occasions.
MCL
Maximum Contaminant Level: The highest level of a contaminant that is allowed in drinking water. MCLs are set as close to the MCLGs as feasible using the best available treatment technology.
MCLG
Maximum Contaminant Level Goal: The level of a contaminant in drinking water below which there is no known or expected risk to health. MCLGs allow for a margin of safety.
MFL
million fibers per liter
MRDL
Maximum residual disinfectant level: The highest level of a disinfectant allowed in drinking water. There is convincing evidence that addition of a disinfectant is necessary for control of microbial contaminants.
MRDLG
Maximum residual disinfectant level goal: The level of a drinking water disinfectant below which there is no known or expected risk to health. MRDLGs do not reflect the benefits of the use of disinfectants to control microbial contaminants.
mrem/year
millirems per year (a measure of radiation absorbed by the body)
NTU
Nephelometric Turbidity Units
pCi/l
picocuries per liter (a measure of radioactivity)
ppm
parts per million, or milligrams per liter (mg/l)
ppb
parts per billion, or micrograms per liter (ug/l)
ppt
parts per trillion, or nanograms per liter
ppq
parts per quadrillion, or picograms per liter
PHGS
PHGS: Public Health Groundwater Standards are found in NR 140 Groundwater Quality. The concentration of a contaminant which, if exceeded, poses a health risk and may require a system to post a public notice.
RPHGS
RPHGS: Recommended Public Health Groundwater Standards: Groundwater standards proposed by the Wisconsin Department of Health Services. The concentration of a contaminant which, if exceeded, poses a health risk and may require a system to post a public notice.
SMCL
Secondary drinking water standards or Secondary Maximum Contaminant Levels for contaminants that affect taste, odor, or appearance of the drinking water. The SMCLs do not represent health standards.
TCR
Total Coliform Rule
TT
Treatment Technique: A required process intended to reduce the level of a contaminant in drinking water.
Detected Contaminants
Your water was tested for many contaminants last year. We are allowed to monitor for some contaminants less frequently than once a year. The following tables list only those contaminants which were detected in your water. If a contaminant was detected last year, it will appear in the following tables without a sample date. If the contaminant was not monitored last year, but was detected within the last 5 years, it will appear in the tables below along with the sample date.
Disinfection Byproducts
Contaminant (units)
Site
MCL
MCLG
Level Found
Range
Sample Date (if prior to 2023)
Violation
Typical Source of Contaminant
HAA5 (ppb)
TTHM - HA 19
60
60
1
1
No
By-product of drinking water chlorination
TTHM (ppb)
TTHM - HA 19
80
0
2.5
2.5
No
By-product of drinking water chlorination
Inorganic Contaminants
Contaminant (units)
Site
MCL
MCLG
Level Found
Range
Sample Date (if prior to 2023)
Violation
Typical Source of Contaminant
NITRATE (N03-N) (ppm)
10
10
2.83
0.27 - 2.83
No
Runoff from fertilizer use; Leaching from septic tanks, sewage; Erosion of natural deposits
SODIUM (ppm)
n/a
n/a
6.67
5.35 - 6.67
No
n/a
Contaminant (units)
Action Level
MCLG
90th Percentile Level Found
# of Results
Sample Date (if prior to 2023)
Violation
Typical Source of Contaminant
COPPER (ppm)
AL=1.3
1.3
0.1770
0 of 10 results were above the action level.
No
Corrosion of household plumbing systems; Erosion of natural deposits; Leaching from wood preservatives
LEAD (ppb)
AL=15
0
0.00
0 of 10 results were above the action level.
No
Corrosion of household plumbing systems; Erosion of natural deposits
Radioactive Contaminants
Contaminant (units)
Site
MCL
MCLG
Level Found
Range
Sample Date (if prior to 2023)
Violation
Typical Source of Contaminant
GROSS ALPHA, EXCL. R & U (pCi/l)
15
0
5.3
0.0 - 5.3
3/24/2020
No
Erosion of natural deposits
RADIUM, (226 + 228) (pCi/l)
5
0
1.6
0.4 - 1.6
3/24/2020
No
Erosion of natural deposits
GROSS ALPHA, INCL. R & U (n/a)
n/a
n/a
5.7
1.4 - 5.7
3/24/2020
No
Erosion of natural deposits
COMBINED URANIUM (ug/l)
30
0
0.7
0.6 - 0.7
3/24/2020
No
Erosion of natural deposits
Unregulated Contaminants
Unregulated contaminants are those for which EPA has not established drinking water standards. The purpose of unregulated contaminant monitoring is to assist EPA in determining the occurrence of unregulated contaminants in drinking water and whether future regulation is warranted. EPA required us to participate in this monitoring.
Contaminant (units)
Level Found
Range
Sample Date (if prior to 2023)
1,2,4-TRIMETHYLBENZENE (ppb)
17.00
17.00
1,3,5-TRIMETHYLBENZENE (ppb)
5.10
5.10
TERT-BUTYLBENZENE (ppb)
2.50
2.50
O-CHLOROTOLUENE (ppb)
3.50
3.50
P-CHLOROTOLUENE (ppb)
0.55
0.55
1,1,1,2-TETRACHLOROETHANE (ppb)
26.00
26.00
ISOPROPYLBENZENE (ppb)
0.67
0.67
N-PROPYLBENZENE (ppb)
4.00
4.00
Volatile Organic Contaminants
Contaminant (units)
Site
MCL
MCLG
Level Found
Range
Sample Date (if prior to 2023)
Violation
Typical Source of Contaminant
ETHYLBENZENE (ppb)
700
700
1.6
0.0 - 3.1
No
Discharge from petroleum refineries
STYRENE (ppb)
100
100
0.1
0.0 - 0.3
No
Discharge from rubber and plastic factories; Leaching from landfills
TOLUENE (ppm)
1
1
0.0160
0.0000 - 0.0320
No
Discharge from petroleum factories
XYLENES, TOTAL (ppm)
10
10
0.0095
0.0000 - 0.0190
No
Discharge from petroleum factories; Discharge from chemical factories
Additional Health Information
If present, elevated levels of lead can cause serious health problems, especially for pregnant women and young children. Lead in drinking water is primarily from materials and components associated with service lines and home plumbing. Dickeyville Waterworks is responsible for providing high quality drinking water, but cannot control the variety of materials used in plumbing components. When your water has been sitting for several hours, you can minimize the potential for lead exposure by flushing your tap for 30 seconds to 2 minutes before using water for drinking or cooking. If you are concerned about lead in your water, you may wish to have your water tested. Information on lead in drinking water, testing methods, and steps you can take to minimize exposure is available from the Safe Drinking Water Hotline or at www.epa.gov/safewater/lead.
Other Compliance
Monitoring Violations
Description
Contaminant Group
Sample Location
Compliance Period Beginning
Compliance Period Ending
Chem M/R - Reg - No Regular samples
Volatile Organic Contaminants
1
7/1/2023
9/30/2023
We are required to monitor your drinking water for specific contaminants on a regular basis. Results of regular monitoring are an indicator of whether or not your drinking water meets health standards. During the compliance period noted in the above table, we did not complete all monitoring or testing for the contaminant(s) noted, and therefore cannot be sure of the quality of your drinking water during that time.
Actions Taken
We were late with one monthly water report this past year and it was done and submitted.